Study the Performance of Different Packing in Open Cooling Towers

Authors

  • Mohammed Nsaif Abbas Environmental Engineering Department, College of Engineering, Al-Mustansiriyah University, Baghdad, Iraq Author

Keywords:

cooling tower, packing, corrugate packing, grid packing

Abstract

The effect of different shapes (corrugate, and grid) of packing on the performance in air -water-cooling tower were addressed in this research. A mechanical forced draught counter current flow-cooling tower of (40 * 40) cm cross-sectional area and 1.5 m high was constructed. Airflow rates of 0.4,1.4, and 2 kg/m2.s were used in conjunction with water flow rates of 1.5, 2, and 2.5 kg/m2.s, and water temperature of 40, 45, 50 0C. The tower characteristics (KG a Z/L) over all volumetric mass transfer coefficient(KGa) volumetric heat transfer coefficient in gas phase (hGa) and volumetric heat transfer coefficient in liquid phase (hla) are found to be a function of the water and airflow rates simultaneously. The numerical analysis was done by preparing computer program to reduce each set of data obtain form the plant and to evaluate the performance coefficient, volumetric owns transfer coefficient, volumetric heat transfer coefficient.The work was extended to include the longitudinal and transverse temperature profiles within the tower for different parameters. By employing packed heights of 100, 75, 50 and 25 cm, end effects were studied, and the tower characteristics (KG a Z/L) corrected from these effects. Least square method was used to correlate the experimental results for (KG a Z/L) in terms of air flux G and water flux L.

   

Downloads

Key Dates

Published

2012-06-01

How to Cite

Nsaif Abbas, M. . (2012). Study the Performance of Different Packing in Open Cooling Towers. Journal of Engineering and Sustainable Development, 16(2), 193-210. https://jeasd.uomustansiriyah.edu.iq/index.php/jeasd/article/view/1210

Similar Articles

1-10 of 76

You may also start an advanced similarity search for this article.