USING TIO2 NANOFLUID FOR ENHANCING PERFORMANCE OF A WATER CHILLER

Authors

  • Qasim Saleh Mahdi Mechanical Engineering Department, Mustansiriyah University, Baghdad, Iraq Author
  • Sahar Abd Al-Fattah Abood Mechanical Engineering Department, Mustansiriyah University, Baghdad, Iraq Author
  • Baydaa Jaber Nabhani Mechanical Engineering Department, Mustansiriyah University, Baghdad, Iraq Author

Keywords:

Alternative refrigerant, Nanofluid, COP

Abstract

In the present work, an experimental study is carried out to enhance the performance of the water chiller system by using nanofluid (water+TiO2 ) on the shell side of the chiller with different volume concentrations (0.05%, 0.075%, and 0.1%). Experimental work includes two parts; In the first one COP of the system is calculated by using two alternative refrigerants (R-407c and R-134a). In the second part, the optimum COP is found using various concentrations of TiO2 nanofluid for systems with an alternative refrigerant. Experimental results show that the COP of R-134a is better than R407c which will be used in the second part of the present study with nanofluid on the shell side of the system. The COP with (0.1%) nanofluid has been found to increase by (8.5%).

Downloads

Key Dates

Published

2015-09-01

How to Cite

Saleh Mahdi, Q. ., Abd Al-Fattah Abood, S. ., & Jaber Nabhani, B. (2015). USING TIO2 NANOFLUID FOR ENHANCING PERFORMANCE OF A WATER CHILLER. Journal of Engineering and Sustainable Development, 19(5), 16-27. https://jeasd.uomustansiriyah.edu.iq/index.php/jeasd/article/view/799