CONDUCTIVITY BEHAVIOR FOR THE PERMEATE STREAM OF REVERSE OSMOSIS WATER IN THERMAL POWER STATION

Authors

  • Suha Anwer Ibrahim Environmental Engineering Department, Mustansiriyah University, Baghdad, Iraq Author

Keywords:

Reverse osmosis water, pretreatment in thermal power station

Abstract

The study deals with the conferences of the Reverse Osmosis membrane of water treatment unit in AL-Doura thermal power station in Baghdad. The study concerned the analysis of RO water by the most convenient analytical equipments. From May 2015 to May 2016 over one year samples quality of the RO water in AL-Doura thermal power plant was accomplished .The results show that the lowest conductivity average values in the 1st quarter at day and at night. The greatest conductivity average values in the 3rd quarter at day and at night. In general the operation of reverse osmosis unit in Al-Doura thermal power station are in compliance with the restriction specifications of manufactured company design manual but in some days in hot months are not in the range.

Downloads

Published

2019-01-01

How to Cite

CONDUCTIVITY BEHAVIOR FOR THE PERMEATE STREAM OF REVERSE OSMOSIS WATER IN THERMAL POWER STATION. (2019). Journal of Engineering and Sustainable Development, 23(1), 80-92. https://jeasd.uomustansiriyah.edu.iq/index.php/jeasd/article/view/260